Summary of main protection design for hydro-generators of Xiangjiaba power station and Xiluodu power station
Lin GUI,Xiangheng WANG,Yuguang SUN,Weijian WANG,Jiang MAO,Zhipeng YUAN,Jiwei MU
DOI: https://doi.org/10.3969/j.issn.1006-6047.2010.07.005
2010-01-01
Abstract:Twenty-six large-sized hydraulic generators of five different stator winding types with the rating between 770 MW and 800 MW are equipped in Xiluodu and Xiangjiaba power stations. It is found that, though the neutral point leading mode, main protection configuration scheme and protection performance of these generators are quite different, the quantitative and optimal design of generator main protection simplifies the hydraulic generator with even or odd branches into that with two or three branches per phase and groups the branches rationally according to the fault features and the branch amount per phase; the performance of protection configuration scheme is dependent of the stator winding type, which should be considered during the stator winding type selection to meet the requirements of both machine design and protection.