New Progress of Design and Setting of the Generator Transformer Protection for Qingyuan Pumped Storage Power Station

GUILin,WANGFeifei,WANGXiangheng
DOI: https://doi.org/10.3969/j.issn.1671-3893.2016.04.004
2016-01-01
Abstract:As Qingyuan pumped storage power station has already put into operation,it’s necessary to make a summary of the new advances in its design and settings of the generator-transformer unit protection Based on the comprehensive internal fault simulation and with consideration of the generator design and the instal ation of CT,the quantitative and optimization design of main protection for Qingyuan generator has been completed; By adding new trip-permitted current components, the ability of SIEMENS generator out-of-step protection to distinguish between out-of-step oscillation and stable oscil ation has been enhanced; When it comes to the protection settings of generator stator ground fault and low voltage side of main transformer ground fault,the change in generator’s capacitance and low voltage side of main transformer’s capacitance brought by GCB interrupting operation is taken into consideration. Above experiences can be used as a reference for the construction of pumped storage power station in the future.