Reconsideration of the Main Protection Scheme of Internal Faults for No.1 Generator in the Three Gorges Power Station

桂林,王祥珩,王维俭,张学深
DOI: https://doi.org/10.3969/j.issn.1674-3415.2001.09.003
2001-01-01
Abstract:Based on the simulation of all kinds of slot and end faults of No.1 generator in the Three Gorges Power Station, the paper analyzes the difference of sensitivity between the combination of two kinds of zero-sequence current transverse differential protection, incomplete split-phase transverse differential protection and two kinds of incomplete longitudinal differential protection and the combination of two kinds of zero-sequence current transverse differential protection, traditional (complete) split-phase transverse differential protection and two kinds of incomplete longitudinal differential protection. Then the main protection scheme of internal faults is proposed for No.1 generator in the Three Gorges Power Station.