Sensitivity Analysis of Incomplete Split-Phase Transver se Differential Protection for Three Gorge Power Station

Wei-jian WANG,Lin GUI,Xiang-heng WANG
DOI: https://doi.org/10.3969/j.issn.1006-6047.2001.04.001
2001-01-01
Abstract:For No.1 and No.2 generators of Three Gorge Power Station all possible slot and end faults are respectively calculated by multi-loop method. Based on that, the sensitivities of traditional (complete )and incomplete split-phase transverse differential protections are calculate d for each fault condition. The possible operation times, sensitive operation ti mes and non-operation times are counted for these two protection schemes, and then the non-operation faults are classified. With the calculation and statistic results, the sensitivity difference between the two protection schemes for gene rators with different structure are analyzed.
What problem does this paper attempt to address?