Voltage Features Based Open-phase Protection of Generator Circuit Breaker

LI Heting,GUI Lin,HE Rufei,CHEN Jun
DOI: https://doi.org/10.7500/AEPS20160121008
2017-01-01
Abstract:In view of the failure of Guangzhou Pumped Storage Power Station A (GPSPSA) generator circuit breaker (GCB) to shave the fault during single-phase disconnection that led to expansion of the accident when the generator was running under low load, the symmetrical component method is adopted to analyze the GCB open-phase fault.The simulation model for the GCB open-phase fault is built using the PSCAD software.According to the fault features, the phase angle difference of the zero sequence fundamental voltages between the two sides of GCB is assumed to be the new criterion for GCB open-phase protection.Through the experiment of the dynamic simulation system for the GCB open-phase fault, the simulation model is verified to be correct and the new criterion for the GCB open-phase protection is rational.