A novel protection scheme for two-phase faults in power distribution system with neutral ungrounded

Shengxing Shi,Aoyu Lei,Xin Li,Xinzhou Dong
DOI: https://doi.org/10.1049/cp.2014.0051
2014-01-01
Abstract:A novel protection scheme for two-phase faults in power distribution system with neutral ungrounded is presented. The feasibility of tripping single-phase circuit when a phase-to-phase or two-phase-to-ground fault occurs is studied with induction motor loads as the focus. The paper at first analyses the effect of a induction motor runs with one phase cut off theoretically. And then a real power distribution system model with 110kV, 35kV and 6kV voltage levels is built in PSCAD/EMTDC. Three feasibility criteria are proposed for motors in continuous operation with single-phase opened. At last, the novel protection scheme is testified in simulation with protection time and reclosing time as variables respectively. The results verify that the scheme is feasible and power supply reliability is improved.