Ground fault protection algorithm of active distribution network based on energy extremum direction
Li Jun,He Min,Huang Shoudao,Wu Xuan,Fan lv,Liu Zhi Yong
DOI: https://doi.org/10.1049/gtd2.13288
2024-10-03
IET Generation Transmission & Distribution
Abstract:Following the large‐scale integration of distributed power sources into distribution networks, fault currents undergo noticeable changes, which impacts the accuracy of conventional single‐phase ground fault algorithms. To tackle these issues, this work initially proposes an active distribution network ground fault protection algorithm based on the direction of extreme energy. Then, by establishing the electrical system structure and model of distribution network ground faults in the presence of distributed power sources, theoretical derivations and computations of transient zero‐sequence current frequency variations during fault instances are carried out. The characteristics of zero‐sequence current directions under distributed power sources integration are analysed, facilitating the design of a local ground fault determination algorithm grounded in the principle of energy extremum direction. This includes outlining fault determination and isolation procedures for ground fault monitoring equipment. Finally, through simulation testing, it is proven that the algorithm can reliably detect ground faults under both neutral point grounding configurations involving an arc suppression coil and ungrounded systems, across a range of transition resistances, varying numbers and capacities of distributed power sources connected, and differing grounding switch operation angles. After large‐scale distributed power sources are connected to the distribution network, the fault current undergoes noticeable changes, affecting the accuracy of traditional single‐phase grounding fault algorithms. Therefore, the objective of this paper is to address the impact of distributed power integration on the grounding algorithms of distribution networks. The main contribution is: by establishing an electrical system structure and model for distribution network grounding faults that include distributed generation (DG), theoretically deriving and calculating the transient zero‐sequence current frequency changes at the moment of fault, analysing the directional characteristics of zero‐sequence currents under DG connection conditions, designing a local grounding fault judgment algorithm based on energy extremum direction, and providing a fault judgment and isolation process for grounding fault monitoring devices. The results show: through simulation and experimentation, the algorithm was tested, and the method can reliably judge grounding faults under various transition resistances, different numbers and capacities of connected distributed power sources, and different grounding switch‐on angles. The applicability of the algorithm covers both methods of neutral grounding through an arc suppression coil and ungrounded neutrals, adapting to scenarios with or without DG connections.
engineering, electrical & electronic