Single-phase Grounding Fault Line Selection Method of Ring Distribution Network Based on Classification Method

Shijun Chen,Chengyao Cui,Yongquan Hou,Qiang Song,Shuang Mei
DOI: https://doi.org/10.1145/3495018.3495525
2021-01-01
Abstract:Considering the reliability of the distribution network, China's low- and medium-voltage distribution network adopt low-current grounding methods. Single-phase grounding faults frequently occur in small-current grounded distribution networks, and the fault characteristics are weak, which causes great difficulties in line selection and positioning. When single-phase arc ground faults and steady-state ground faults occur in the feeder of the new distribution network in closed-loop operation and closed-loop lines, by observing the fault zero sequence current, a closed-loop operation based on classification is proposed. According to the method, the transient state information, the steady-state information and the information of two ends of a loop line which is in fault are effectively utilized; and simulation verification proves that this method is able to choose the fault line, improve the accuracy, and can not be influenced by factors such as the impedance of fault point and has higher value.