Analysis of Single-phase Open Fault for Resonant Grounded System
Hongtao ZHANG,Lili CAO,Guang FENG,Yongduan XUE,Ning ZHOU,Peng WANG
DOI: https://doi.org/10.3969/j.issn.1003-8930.2019.02.013
2019-01-01
Abstract:The number of open faults on distribution lines is increasing year by year;however,simple and effective de?tection methods are scarce. In this paper,based on a resonant grounded system,a model of single-phase open fault is established,which takes into account the location of break points,the ratio of fault line grounding capacitance to sys?tem grounding capacitance,and the magnitude of load impedance. Moreover,the changing characteristic of voltage at neutral point,phase voltages,and line voltages on the supply and load sides are analyzed. Results show that there is a significant difference in the fault phase voltage,but the voltage changes in healthy phases are identical;the line voltag?es on the supply side are almost unchanged,while on the load side,the sum of amplitude of line voltages between the fault phase and two healthy phases is equal to that of the line voltage between two healthy phases,with phases being op?posite or identical. Finally,the theoretical analysis is verified by MATLAB simulation. The research results in this pa?per can provide a theoretical basis for the detection and location of single-phase open fault in the resonant grounded sys?tem.