Faulty line selection based on transient wavelet energy for non-solid-earthed network
Lepeng Wu,Chun Huang,Dabin Lin,Zhijun Zhu,HongTao Jiang
DOI: https://doi.org/10.3969/j.issn.1006-6047.2013.05.013
2013-01-01
Abstract:The fault characteristics of transient zero-sequence network are analyzed in detail, which demonstrates that, the energy spectrum of fault near phase-voltage peak is different from that of fault near zero-crossing point. Aiming at the inaccurate selection of faulty line of non-solid-earthed network when fault occurs near the zero-crossing point of phase voltage, a method of faulty line selection based on transient wavelet energy is proposed, which carries out the wavelet transform of transient zero-sequence current for each feeder, calculates the high-and low-frequency wavelet energies according to the wavelet coefficients, and selects the faulty line according to the maximum value of high-or low-frequency energy. Results of EMTP simulation show that, the proposed method is immune to the closing angle, fault distance, transition resistance, arc, system operating mode, etc., and the faulty line can be accurately and reliably selected when the single-phase grounding fault occurs with high resistance at the end of line or the fault occurs near the zero-crossing point of phase voltage.