Single-phase Grounding Fault Detection Method in Resonant Grounding System Based on Phase Current Variation

Jiangxiong Wu,Maoran Zheng,Guoyan Yang,Xin Wang,Haifeng Li
DOI: https://doi.org/10.1109/apet59977.2023.10489023
2023-01-01
Abstract:To address the problem of weak fault characteristics during single-phase grounding faults in distribution network, this paper proposes a fault detection method for resonant grounding systems based on phase current variation. Based on the fault faulty superimposed component network, and then the expression for phase current variation is derived. Subsequently, the criteria based on ratio of phase current variation is formulated. A fault detection method for resonant grounding systems based on phase current variation is proposed and a fault detection flowchart is provided. Finally, different fault conditions are set in the simulation software to test this method. The results show that under the conditions of different fault locations, fault phases, fault impedance and system compensation levels, the fault detection method based on phase current variation can quickly and accurately identify the fault line and has the ability to resist interference.