Single-phase-to-ground fault section location in flexible resonant grounding distribution networks using soft open points

Zhengtian Li,Yuqing Ye,Xiao Ma,Xiangning Lin,Feng Xu,Chaoliang Wang,Xiaojun Ni,Chao Ding
DOI: https://doi.org/10.1016/j.ijepes.2020.106198
2020-11-01
Abstract:<p>Resonant grounding (RG) distribution networks operate with low fault currents during single-phase-to-ground (SPG) faults. This mode offers a continuous power supply but causes intensifying fault location problems. Overcurrent relays fail to work, and most of the existing location methods are inapplicable. This paper proposes a method based on low-frequency signal superposition to locate SPG faults in RG distribution systems. In this method, a soft open point (SOP), a high-profile power electronic device applied in flexible distribution networks, is used as a signal superposition device, which enhances its existing functions of power and voltage regulation. It superimposes a 25 Hz symmetrical three-phase voltage onto the network after SPG faults occur. The 25 Hz zero-sequence currents along lines are subsequently gathered to determine the fault section. The main feature of the method lies in the adaptive current criterion for fault section location. The analysis of the zero-sequence currents in the low-frequency RG subsystem indicates that the criterion is not sensitive to line parameters, network structure, fault resistance or distributed generation. Comparative simulation tests with the S-injection method in PSCAD confirmed the validity and superiority of the proposed method.</p>