Fault Location Based on Synchronous Data of Both Ends in Non-effectively Grounded System

Jing YUAN,Lin CHENG,Hong-tao LI,Ren-le HUANG
DOI: https://doi.org/10.3969/j.issn.1005-2992.2015.02.006
2015-01-01
Abstract:Because of the sectionalized switches,each feeder of the distribution network is divided into several sections. The single-phase fault may not be effectively and efficiently detected based on existing approaches. The paper puts forward a fault location method based on synchronous data of both ends,on the basis of analy-zing zero sequence current of both ends and differential characteristics of sound section and fault section. The positioning method is implemented by using the synchronous measurement divice with distribution automation ( DA) system. The proposed method is experimented based on the Real Time Digital Simulator ( RTDS ) system. Simulation results demonstrate that the proposed method has better robustness in non-effectively grounded system when coping with uncertainties such as feeder length or transition resistance.