Single-end Fault Location Technique for DC Distribution Lines Based on Network Topology and Measured Traveling Waves

Zhong Liu,Hengmen Liu,Kaixin Zhang,Shenxing Shi
DOI: https://doi.org/10.1109/ciced56215.2022.9929171
2022-01-01
Abstract:In the flexible DC distribution network without DC circuit breaker, due to the poor ability of power electronic components to withstand fault current, it is required to quickly detect the fault, lock the converter and turn off the fault current, which leads to the limited data left for fault location. The root cause of the fault is the addition of a fault branch in the system, which causes the change of network topology and the change of electrical quantity. This paper uses the measured traveling wave to identify the topological difference between the normal network and the post fault network, extracts the reflected wave head only from the fault point, and determines the fault location according to the time of the reflected wave head. Simulation results show that the proposed method is feasible and has high accuracy.
What problem does this paper attempt to address?