Single-ended traveling wave based fault location for single-phase-to-ground in power distribution lines

Yiming Zhao, Shenxing Shi, Guangmei Zhang, Hao Ma, Xinzhou Dong
DOI: https://doi.org/10.1049/cp.2020.0080
2020-01-01
Abstract:Accurately identifying the traveling wave reflected by the fault point is the key to single-ended traveling wave based fault location. Affected by the complex structure and branch lines of the power distribution line, the identification of the traveling waves reflected by the fault point is very difficult. This paper proposes a single-ended fault location for single-phase-to-ground in power distribution lines using switches reclosure generated travelling waves. The paper analyses the difference of travelling waves in three independent line-mode networks and constructs the travelling wave reflected by the fault point directly. And the distance to the fault point from the measuring point is calculated according to the time of switch reclosure generated initial wave and the reflected wave by the fault point. This method is not affected by branch lines and transition resistance. PSCAD simulations verify the accuracy and reliability of the method.