Single-ended Assembled Fault Location Method and Application Considering Secondary Circuit Transfer Characteristics

XU Fei,DONG Xinzhou,WANG Bin,SHI Shenxing
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2015.20.011
2015-01-01
Abstract:Identification and verification of the wave fronts is the precondition of single-ended travelling wave based fault location methods. The fault locators can obtain the data only from the secondary circuit which consists of the current transformer, the secondary cable and the secondary load. Therefore, transfer characteristics of the secondary circuit must be studied first. The high frequency model of the secondary circuit was built and the transfer function was obtained. The damped oscillation in the recorded traveling waves was explained. Based on the discovery, a single-ended fault location scheme involving an impedance fault location algorithm, the dyadic wavelet transform and Prony analysis was proposed in the paper. Relevant traveling wave fault locator was developed and implemented in a 220 kV substation. Recorded waveforms of a single-phase-to-ground fault has proved both the analysis and the location scheme. Abundant simulation results based on EMTP/ATP have also demonstrated the validity and improvement of the novel assembled single-ended fault location method.
What problem does this paper attempt to address?