A Two-Terminal Fault Location Algorithm Using Asynchronous Phasors Based on Distributed Parameter Model

施世鸿,何奔腾
2008-01-01
Abstract:Based on distributed parameter model of power transmission line, a new two-terminal fault location algorithm in which asynchronous phasors are used is proposed. According to the superposition principle of electric circuits, the post-fault power network is equivalent to the superposition of network in normal state and that composed by fault components;then taking single-phase system for example, the fault distance and asynchronous time are taken as unknown numbers and the fault location equations for normal voltage and current phasors as well as fault components are established;and then the analytical expression for fault distance is deduced, in addition the recognition method of false root is given. The applicability of the proposed method in three-phase system is analyzed. ATP-EMTP based simulation results show that the proposed method can eliminate the influence of asynchronous time and is suitable to all types of faults, the fault location is accurate and the computation amount is little, in addition, it is not needed to identify the faulty phase or fault type and the problem of data asynchronization in two-terminal fault location is solved well.
What problem does this paper attempt to address?