New two-terminal fault location algorithm based on instantaneous measurement of power system frequency

Zheng Chen,Xinzhou Dong,Chengmu Luo
2001-01-01
Abstract:Fault location of transmission lines is of much importance for electric power system operation. But all of algorithm of fault location based on power frequency quantity takes the power system frequency as being constant. In fact, the power system frequency is changing, and the change of frequency will lead to great error of fault location. This paper presents a new two terminal fault location algorithm based on instantaneous measurement of power system frequency. This algorithm is suitable to the case of frequency deviation. The results of EMTP simulation show that this algorithm eliminates the effect of frequency deviation for fault location and implement the precision of fault location.
What problem does this paper attempt to address?