Time Domain Fault Location Method Based on Transmission Line Parameter Identification Using Two Terminals Data

Jia-le SUONAN,Yi-ning ZHANG,Jun QI,Zai-bin JIAO
DOI: https://doi.org/10.3321/j.issn:1000-3673.2006.08.013
2006-01-01
Abstract:A time domain fault location method based on transmission line parameter identification using two terminals data is proposed. As for the proposed algorithm, whether the known line parameters, such as resistance, inductance and capacitance, are accurate or not is of no importance. Taking the resistance, inductance and capacitance of transmission line as the parameters to be identified, the voltage distribution along the line is calculated by the current and voltage values sampled at the two terminals. Using the basic principle that only at the faulty point the voltages calculated from both terminals can be equal while fault occurs on the line, accurate line parameters can be recognized and then the faulty point can be calculated, thus the fault location error of traditional fault location method caused by inaccuracy of line parameters is avoided. In the proposed method the result of fault location is expressed by the percentage corresponding to the ratio of fault distance to whole-length of transmission line, and the location result is not influenced by variation of season and sagging in line, so it is convenient to determine the faulty location by ground distance between the towers. ATP simulation shows that the proposed method is much more accurate than traditional methods.