Fault Locating Algorithm for T-type Transmission Lines with Asynchronous Sampling

施世鸿,何奔腾
DOI: https://doi.org/10.3969/j.issn.1006-6047.2008.10.014
2008-01-01
Abstract:A fault locating algorithm for T - type transmission lines with asynchronous sampling is proposed,which is based on distributed parameter model. It uses positive sequence voltage to identify the faulty branch and simplifies the healthy branches to calculate the equivalent electrical quantities of T point. The fault can be located with two - terminal asynchronous sampling methods. The asynchronous sampling time and fault distance are treated as the unknown variables,which are solved by establishing the fault locating equations using the positive and negative components for asymmetric fault and the healthy and faulty positive components for 3-phase symmetric fault. It does not need iteration and search,and avoids the error caused by asynchronous sampling. It has low computation load and is suitable for all fault types without faulty phase identification. The results of ATP-EMTP-based simulation indicate that,the proposed method has high accuracy even with low sampling rate and large fault transition impedance.
What problem does this paper attempt to address?