A Fault Location Method for Multi-branch Distribution Lines.
Kai Wang,Jun Wang,Cheng Chang,Jing Zhang,Lixuan Jia,Jinquan Zhao
DOI: https://doi.org/10.1109/FSKD.2018.8686870
2018-01-01
Abstract:The distribution network structure is complex, the scale is large, the fault rate is high, the fault resistance is relatively large, and the branch is quite a lot, so that the fault signal is hard to detect effectively and the accurate fault location is very difficult to realize. Although there are impedance method, traveling wave method and other fault location methods, these methods have their own conditions. Therefore, the method of artificial line inspection is often used to locate fault. Based on the distribution parameter model of the transmission line, this paper proposed a fault location method for multi-branch distribution line. In this method, the relationship between the voltage and current along the transmission line and at the endpoints of the line is deduced by the transmission line equations. The location of the fault point is obtained according to the voltages at fault point are equal, which are calculated by the voltage and current at two endpoints separately. This method is simple because in the case of known line parameters, it only needs to measure the voltage and current at each endpoint of the line synchronously. Through locating the single-phase ground fault in multi-branch distribution line, the results prove the correctness and accuracy of this method.