Fault Location for Two-Terminal Transmission Lines Using Voltages Phasor

赵伟,王波
DOI: https://doi.org/10.3969/j.issn.1001-4551.2009.05.007
2009-01-01
Abstract:Aiming at the problem of fault location in the power system,an fault location algorithm using synchronized voltage phasor was proposed.Basing on symmetrical component method and linear superposition principle,the additional positive sequence network was established.Then the balance index on fault point was proposed and with this index the fault was located by traversing search method.By only using synchronized voltage phasor,the fault location accuracy of this method was not affected by the saturation of current transformer.The simulations carried out by PSCAD justify that this method can effectively locate the fault and is not affected by types of faults and transition resistances.
What problem does this paper attempt to address?