Fault Location for HV Three-terminal Transmission Lines

SHI Shi-hong,HE Ben-teng,ZHANG Wu-jun
DOI: https://doi.org/10.3321/j.issn:0258-8013.2008.25.018
2008-01-01
Abstract:All of the fault location methods currently used for teed lines need to identify the fault section first,then convert the three-terminal line to a two-terminal line to locate the fault.The fact that while the fault occurs near the teed node,especially through a large resistance,the fault location methods currently used can’t identify the fault section correctly,thus fail to locate the fault was pointed out.Considering the above,a new fault location method for teed lines,which makes use of the pure resistive characteristic of fault impedance is presented.This method breaks the mold of traditional methods that it must identify the fault section before locating the fault.The proposed method can locate the fault without identifying the fault section first.And this method doesn’t have dead zone of fault location,it can accurately locate the fault occurring near the teed node.The accuracy is independent of fault resistance and fault type.Above all,this method perfectly solves the disadvantage of currently used methods that there is a dead zone of fault location near the teed node.Results of EMTP based simulation indicate that this method is correct and accurate.