An Identification Method of Single-phase Permanent Fault at Transmission Lines with Shunt Reactors

wang qingqing,wang huifang,lin da,he benteng
DOI: https://doi.org/10.7500/AEPS20140118001
2015-01-01
Abstract:Based on the transmission characteristics of extra high voltage(EHV)transmission lines with shunt reactors,a new algorithm for calculating transition resistance through a distributed parameter model is presented.In view of the case of permanent fault where the transition resistance is basically fixed at a low value,whereas in the case of transient fault,where after the arc is extinguished,the calculated value of transition resistance immediately increases to a large value,we are enabled to distinguish the fault nature,and the extinction time of secondary arc as well.This method can work just by making use of the current of shunt reactors and the non-fault-phase at one terminal,and fault location results,and is easy to use.Electromagnetic transient program simulation results and analyses show that the method is hardly affected by fault location,load current and transition resistance,and can be applied to transmission lines with shunt reactors at one terminal and at both terminals.What’s more,the method can withstand the inaccuracy of fault location,transmission line parameters,and system frequency to some degree.