Estimation of Transient Character for UHV Transmission Line

张波,何奔腾
DOI: https://doi.org/10.3969/j.issn.1006-6047.2010.05.001
2010-01-01
Abstract:Based on the lab research of main frequency theory,the main frequency component character of transient noise is analyzed,which concludes that:the main frequency is inversely proportional to fault distance and system impedance whereas its current amplitude is directly proportional to them. An intuitive estimation method of transient character is put forward,which gets the analytic expressions of the main frequency and its amplitude by fitting the transient character with the least square method. Simulation and analysis show that,the estimation error of the main frequency is less than 6 % and that of its amplitude is less than 8 % when the fault distance is less than 600 km,which means that the transient character can be analyzed rather accurately and quantitatively. Based on the method,it is further concluded that,the shunt reactor makes the main frequency larger and its amplitude smaller,favorable to transient process,while the increase of voltage grade makes the main frequency smaller and its amplitude larger,harmful to transient process.