Study on the Power Frequency Electromagnetic Field under UHV Transmission Lines

ZHANG Li-ting,HU Bai-xue,ZHOU Hao
DOI: https://doi.org/10.3969/j.issn.1004-3950.2006.04.012
2006-01-01
Energy Engineering
Abstract:The paper models on the real UHV transmission lines of former Russia,and simulates the influence of the height of phase conductors,wire spacing,the number of split conductors,spacing of split conductors and the diameter of the subconductors on the electric field due to UHV transmission lines at ground level using the CDEGS software package.Results show that rising the height of phase conductors,decreasing wire spacing,reducing the number of split conductors,shortening the spacing of split conductors and selecting smaller section of subconductors can all reduce the electric field at ground level,of which rising the height of phase conductors has the best effect.Then the paper also put forward the reduction method of installing extra shield wires beneath the power lines.And the cases of installing 2,3,5 and 7 shield wires were simulated.Results show this method can obviously reduce the electric field at ground level.
What problem does this paper attempt to address?