Calculation of Ground-Level Electric Field and Ion Flow of HVDC Transmission Lines With Shield Wires

QIAO Ji,ZOU Jun,E Tianlong,MA Lei,HU Chuyun
DOI: https://doi.org/10.13335/j.1000-3673.pst.2016.2487
2017-01-01
Abstract:It is an effective way to restrict electric field and ion current on ground level by installing shield wires. Due to space charge, electric field strength on shield wire surface is significantly increased. Therefore, whether corona occurs on the shield wires depends on total electric field rather than space-charge-free field. In this paper, domain decomposition method is used to analyze shielding effect of shield wires. Corona from shield wires is taken into consideration in iteration loop. Different methods are used to predict ground-level electric field and ion current density of a reduced scale model. Calculations are compared with measurements and reasons causing error are analyzed. Results indicate that earth corona will enhance shielding effects because space charges generated from shield wires will recombine with ion current from dc conductors. Earth corona should be taken into consideration in numerical method. Finally, electric field of a typical ±800 kV HVDC transmission line is analyzed and shield wire arrangement is discussed.
What problem does this paper attempt to address?