Influence of Corona Effect on Ground Level Electrical Field under EHV/UHV AC Transmission Lines

李伟,张波,何金良,曾嵘,黎小林,王琦
2008-01-01
Abstract:Corona decides the electromagnetic environment characteristics of transmission line. It is generally considered that the space charges produced by corona discharge are restricted in the vicinity of AC transmission lines and rarely affect the ground level electrical field. So,the corona effect is usually neglected in the calculation of ground level electrical field under AC transmission lines. However,this theory needs to be proved. In this paper,the charge simulation method (CSM) based ion flow field calculation method is improved and applied into the calculation of ground level electrical field under AC transmission lines. The influence of the conductor surface field uniformity on corona discharge is counted in,so that the ion flow field of multi-phase or bundle conductors can be simulated. The ground level electrical field considering corona effect under a 3-phase 8-bundle conductor 1000kV AC transmission line is calculated. The calculation results indicated that the corona discharge enhances the ground level electrical field,and the enhancement ratio is about 5% for typical 3-phase 1000kV AC transmission lines. The influence of line parameters such as bundled conductor radius,split conductor spacing,split conductor number,wire spacing and phase height on ground level electrical field are discussed.