Impact of zero-sequence mutual inductance in UHV Anhui-to-east power transfer lines on phase-earth distance protection

Bo Zhang,Fufeng Chen,Yuting Wang,Mingjun Xue,Benteng He
DOI: https://doi.org/10.7500/AEPS201209115
2013-01-01
Abstract:Distribution characteristics of zero-sequence current when parallel transmission lines grounding fault happens, the impact of zero-sequence mutual inductance on phase-earth distance protection, the setting method of zero-sequence compensation coefficient (K values) in grounding distance protection, and the impact of different K value setting schemes on protecting range of action are analyzed. With the simulation analysis of ultra-high voltage (UHV) 1000 kV Anhui-to-east power transfer parallel transmission lines, change trajectories of fault calculating impedance under different working conditions along the line, the setting reference values and protecting action range of zone I distance with different zero-sequence compensation coefficients are given. Finally, combining with the engineering practice, and considering the setting convenience and the protection sensitivity and safety, referential setting schemes for distance protection related constant values are proposed. ©2013 State Grid Electric Power Research Institute Press.