Influence of DC filter parameters on single-pole grounding faultovervoltage in ±800 kV UHVDC transmission line

苏宜靖,张光明,于竞哲,公衍钊,李济沅,张黎,周浩,王东举,韩雨川
DOI: https://doi.org/10.16189/j.cnki.nygc.2017.02.004
2017-01-01
Energy Engineering
Abstract:The influence mechanism of DC filter parameters on single-pole grounding fault overvoltage was studied based on the electromagnetic coupling between two pole lines and the wave process.The influences of DC filter parameters including capacitance parameters and inductance parameters on the overvoltage as well as the influence regulation were analyzed.The research showed that, the DC filter capacitance parameters had certain influence on single-pole grounding fault overvoltage, and the main capacitor of DC filter influenced the overvoltage most significantly, which was the critical factor to limit the overvoltage on transmission line, while the DC filter inductance parameters had little effect on the overvoltage.The increasing trend of overvoltage tended to be slow with the increase of capacitance parameters.The overvoltage of transmission line could be basically limited within 1.7 times of rated voltage as the main capacitor of DC filter was limited within 2μF.