Lightning Intruding Overvoltage for DC Field of ±800 Kv Zhexi Converter Station

Hao Zhou
2012-01-01
Abstract:The lightning invasion in DC converter station may endanger the safe operation of HVDC system.Based on the ±800 kV UHVDC power transmission project from Xiluodu to Zhexi,the lightning intruding overvoltage for the DC field of Zhexi converter station is simulated and analyzed.Evidently,equipment of negative DC voltage is preferred when calculating equipment′s max voltage to ground,while equipment of positive DC voltage is preferred when calculating max voltage between two terminals of equipment;20 kA negative lightning current is proper to be selected as the lightning amplitude for the calculation of lightning shielding wave in UHVDC converter station;for DC bus overvoltage calculation,the monopolar ground return mode is applicable,and none of the overvoltage levels of the equipments in the converter station exceeds the required level;for DC neutral bus lightning overvoltage calculation,the monopolar metallic return mode can be selected,and the overvoltage levels of the equipments in DC field,terminals of reactor and isolating switch are within the safe operating voltage level,harmless to the operation of converter station.