Study on Neutral-Bus Overvoltage Mechanism of ±500 Kv DC Power Transmission Project from Tianshengqiao to Guangdong

Hao Zhou
2011-01-01
Abstract:Based on post-innovation control and protection strategies for ±500 kV DC power transmission project from Tianshengqiao to Guangdong,the overvoltages of neutral-bus under various fault conditions are researched and the overvoltage processes under different fault conditions are divided into several stages for the detailed analysis,and the overvoltage mechanism as well as the current direction during various stages are expounded.Research results show that the energy flowing through neutral-bus arrester due to the grounding faults respectively occurred at outgoing line of valve side of converter transformer and that occurred at outgoing line of rectifier bridge cannot be controlled by the control and protection system,so the neutral-bus arrester has to exist enough adequate energy capability;the energy flowing through neutral-bus arrester due to the break fault occurred in DC system can be reduced while the time-delay of protection action is shortened.