DC switching overvoltage of ± 1100 kV UHVDC converter station

Xu Deng,Dongju Wang,Yang Shen,Hao Zhou,Xilei Chen,Ke Sun
DOI: https://doi.org/10.3969/j.issn.1006-6047.2014.01.024
2014-01-01
Abstract:The mechanism of switching overvoltage occurred in the valve hall and DC switchyard of ��1100kV UHVDC converter station is analyzed based on Zhundong-Sichuan ��1100 kV UHVDC power transmission project. Different faults are simulated, such as the grounding fault of HV winding of Y/Y converter transformer at valve side, the grounding fault of LV winding of Y/Y converter transformer at valve side, the phase-to-phase switching surge at AC side, the AC power loss at inverter side, the full-voltage starting, the inverter blocking without by-pass de-blocking, and the corresponding overvoltages exerted on the equipments of converter station are calculated, which provide the reference for the type selection, test and insulation coordination of station equipments.
What problem does this paper attempt to address?