Study on overvoltage and insulation coordination of DC filter for ±800 kV UHVDC project from Xiangjiaba to Shanghai

Xilei Chen,ZHOU Hao,WANG Dong-ju,SHEN Yang,QIAN Feng,ZHOU Zhi-chao,DING Jian
2012-01-01
Abstract:Based on the ±800 kV UHVDC project from Xiangjiaba to Shanghai,two typical faults for transient calculation of DC filter including ground fault on the DC line and incoming switching surge on the DC line are presented.The simulation steep-fronted models and factors including protective characteristics of arresters,parasitic inductances of DC bus and DC filter high voltage capacitor which should be considered for these two faults are introduced.The calculation results give the transient stresses for reactors and resistors.The protective levels of arresters are obtained according to the calculated maximum arrester currents,and the withstand levels of the filter equipments are defined at last according to the insulation margin.
What problem does this paper attempt to address?