Research on Power Frequency Over-Voltage in UHV AC Transmission Lines

SUN Ke,YI Qiang,DONG Chaowu,ZHOU Hao
2010-01-01
Abstract:Due to its long transmission distance,high transmission capacity,and high charging power,the power frequency over-voltage level occurred in ultra high voltage(UHV) transmission line is much higher than that occurred in extra high voltage(EHV) transmission line,however the computational conditions for power frequency over-voltage in UHV transmission line are not determinate enough.On the basis of the calculation and analysis of power frequency over-voltage occurred in single-circuit and double-circuit UHV transmission lines,the comparative research on various power frequency over-voltage is performed from different viewpoints and the kinds of power frequency over-voltage,which should be emphatically considered in the research on power frequency over-voltage occurred in single-circuit and double-circuit UHV transmission lines,are decided and corresponding explanations are given in theory.Research results show that as for single-circuit UHV transmission line the over-voltage due to load shedding during single-phase earth fault should be emphatically considered,and as for double-circuit UHV transmission line on the same tower the over-voltage due to load shedding during single-phase earth fault under single-circuit operation mode and the over-voltage due to fault-free load shedding under double-circuit operation mode should emphatically considered.
What problem does this paper attempt to address?