Lightning Performance of Quadruple-circuit Transmission Line with Dual Voltage 500/220 Kv on the Same Tower

周浩,赵斌财,王东举,贾振宏,吴锁平,吴建宏
DOI: https://doi.org/10.13336/j.1003-6520.hve.2008.10.024
2008-01-01
Abstract:The lightning performance of quadruple-circuit transmission line with dual voltage 500/220 kV on the same tower is calculated and analyzed with EGM(Electro-geometrical Model) and EMTP(Elector-Magnetic Transient Program).And the effects of fielding angle,nominal height of the tower,ground elevation,grounding resistance and the way of laying additional shield wires are discussed in detail.In accordance with 500 kV and 220 kV transmission lines on the same tower,the results show that the priority is different for improving lightning performance,namely,the shielding failure is relatively serious for 500 kV transmission line,and the back flashover is relatively serious for 220 kV transmission line.Finally,several special methods that may be used to improve or degrade lightning performance are presented,such as reducing nominal height of the tower,using negative fielding angle and setting up additional shield wires.