Lightning Withstand Performance of the Yun-guang ±800kv UHVDC Power Transmission Line

SHANG Tao,DU Zhong-dong,ZHANG Cheng-wei,LIU Xi
2008-01-01
Abstract:Yun-guang ±800 kV UHVDC power transmission line is the first UHVDC project with ±800 kV voltage and 5 million kW capacity in the world.Lightning protection for the transmission line is arduous for the severe lightning stroke in the area.Based on ATP-EMTP,EGM,models of lightning withstand performances for back striking and shielding failure for UHVDC transmission line are established.Research results show that back striking withstand performance is better than shielding failure withstand performance in Yun-guang ±800 kV UHVDC power transmission line,and the negative shielding angle should be adopted because the principal cause of lightning stroke failure is the shielding failure.Other measures for lightning protection such as lightning rod for shielding failure and coupling ground wire should be installed when the tower is excessively high(higher than 60 m) or the ground obliquity is excessively large(larger than 20°).