Study on Lightning Performance for ±500kV DC Double Circuit Transmission Lines

Nie Ding-zhen
Abstract:This paper studies on lightning performance for (500 kV DC double circuit transmission lines, and tower model for lightning protection performance of shielding failure is proposed. The calculation results of 4 polar layout of double circuit line show that except polarity configuration mode C lightning flashover rates with other three kinds of configuration modes are not more than 0.093 times/(100km·a)(ground slope angle is 15°). This result for DC line which is less than the statistical results of lightning flashover rate for 500 kV AC line(0.1363 times/(100km·a)). The simultaneous tripping rate of double normal polarity is less than single normal polarity. So DC double circuit transmission lines can satisfy the lightning performance requirement. East China aera is a densely populated and developed aera, but lack of land resources. So using the line corridor of the former ±500 kV Genan single circuit line and adopting±500 kV DC double circiut line to transmit power to east China is efficient method to add unit corridor aera transmission capacity. Because the length of double circuit line tower is high ,so its more likely to suffer lightning stroke. So the study on studies on lightning performance for ±500 kV DC double circuit transmission line is necessary. The calculation results demonstrate that ±500 kV DC double circuit transmission line lightning performance can satisfy the operation requirement. When lightning strike tower top, double positive polarity circuit line may occur back strike at the same time.