Approaching to Rotated Lightning Strike on Transmission Line

ZHAO Bin-cai,ZHOU Hao,ZHONG Yi-jun,CHEN Jia-miao,ZHU Tian-hao,ZHANG Li-ting,WANG Jian-min
DOI: https://doi.org/10.16188/j.isa.1003-8337.2008.01.008
2008-01-01
Abstract:Experimental methods and models were analyzed,such as standard method,electrical geometric model(EGM),leader progression model(LPM) and shielding failure probability model.The standard method is easy for satisfactory use in lightning protective shield design for normal lines;electric-geometrical model is rational and easy for analyzing EHV and UHV lines,mountainous lines and multi-circuit lines.The leader progression model and shielding failure probability model give a reasonable interpretation of rotated flashover in physical mean,but they have rather complex calculation procedure and for time being can not be widely used for engineering application at long-distance transmission lines.Detailed discussion was made on relevant parameters of electro-geometrical model,from which the calculation of striking distance and striking distance factor was made using equation recommended by IEEE WG.For regions of mean annual thundery day more than 40,the thundering rate at ground surface can be taken as 0.1 time / km2 thundery day.Based on statistics of thundering number on 35~220 kV in China,the thundering rate for some thunderous regions can be calculated using equation recommended by CIGRE.