Numeral Analysis Model for Shielding Failure of Transmission Line under Lightning Stroke

Jinliang He,Youping Tu,Rong Zeng,J.B. Lee,S.H. Chang,Zhicheng Guan
DOI: https://doi.org/10.1109/tpwrd.2004.839189
IF: 4.825
2005-01-01
IEEE Transactions on Power Delivery
Abstract:The shielding failure is the occurrence of a lightning stroke that bypasses the overhead ground wires and terminates on the phase conductors. The correct design to improve the shielding effect of transmission line to lightning is one of the key problems of transmission line design. A numerical analysis model for shielding failure of transmission line based on electromagnetic field theory is proposed in this paper. The electrical field of the system including lightning leader, transmission line and ground is solved, the range of lightning current striking the phase conductor is obtained, and the shielding failure probability of transmission line is calculated. The lightning leader model and the critical breakdown electrical field intensity of long gap are discussed. The analyzed results by numerical analysis model are compared with those by the electrogeometric model.
What problem does this paper attempt to address?