Calculation of Shielding Failure Flashover Rate of Transmission Line Using Leader Progression Model

Rong ZENG,Hanbo LIU,Chijie ZHUANG,Guojun LU,Jianbin LUO
DOI: https://doi.org/10.13336/j.1003-6520.hve.20170428025
2017-01-01
Abstract:Lightning shielding failure is the key problem for safety and stability of power system.Current models for analysis of lightning shielding failure are simplified in the description of the leader process.Consequently,using the mechanism of positive upward leader inception and propagation,we proposed a criterion of upward leader inception for single and bundle conductors,and proposed a method for calculating streamer space charge considering the variation of background potential.Thereby,we put forward an algorithm and adaptive strategies for calculation of transmission line shielding failure flashover rate using the proposed model,by which the shielding failure characteristics of 500 kV transmission line are analyzed.The result of leader inception agrees with that of Rizk model and critical radius model for low voltage cases.The calculated shielding failure flashover rate of 500 kV transmission line in plain area is 0.012 strokes/(100 km.a),and the value is 0.211 strokes/(100 km·a) for mountainous region,which is consistent with the operation data.The adaptive method is faster than the original method in the same precision.
What problem does this paper attempt to address?