Abstract:Upward leader is one of the key factors for analyzing the shielding failure of lightning,but a number of questions remain to be unanswered because it is difficult to observe the upward leader from transmission lines.In order to research whether the upward leader can incept from the transmission lines,it is necessary to study the characteristics of upward leader.Therefore,models of upward leader are established to calculate the rate of shielding failure by the breakdown voltage of rod-plane gap or theory of thermodynamics,but it is proved that these models are not completely suitable for analyzing the shielding failure of lightning.We presented results from the ultra high voltage laboratory in Kunming.Measurements were conducted in a rod-conductor gap of 5~8min length under maximum voltage of 3.6MV,200/2 000μs impulses,discharge was observed with high speed camera,the current was measured using a current shunt with frequency response of 0~6.5 MHz,and upward leader was observed in the process of discharge.The velocity of upward leader is found to be 1.2~3cm/μs,which is in accordance with the velocity of leader observed in rod-plane gap discharge under positive impulse.The duration of field strength when critical radius of conductors exceeds the critical value is longer than that in the experimental conditions,so the existence of upward leader in the process of shielding failure of lightning is reasonable.