Comparative Research on Z-Type Tower and Traditional T-Type Tower for UHVDC Transmission Lines Located at Mountain Areas

万亦如,陈稼苗,周浩,张彤,苏菲,沈志恒,陆海清
DOI: https://doi.org/10.13335/j.1000-3673.pst.2012.03.013
2012-01-01
Abstract:UHVDC transmission lines in China have to pass through a lot of mountainous regions where lightning strokes frequently occur, thus the shielding failure outage rate of UHVDC transmission line adopting conventional T-type towers and passing through mountainous region is high. For this reason, a new type of tower possessing a new type of tower head, namely the Z-type tower, is designed for the part of UHVDC transmission line from Xiluodu to Zhexi, which passes through mountainous regions. The lightning withstand performances of back flashover and shielding failure of T-type tower and Z-type tower as well as their impacting factors are researched by the simulation in which the calculation model of shielding failure is established by electrical geometry model (EGM) and the calculation model of back flashover is established by ATP-EMTP, meanwhile combining CDEGS software with formula method the electromagnetic environment of Z-type tower is assessed. Research results show that the Z-type tower's lightning withstand performances of back flashover is high, therefore the overall lightning withstand performance of Z-type tower is evidently better than that of T-type tower. Under the lowest nominal height of tower, the electromagnetic environment parameters of Z-type tower can reach national environmental standards and are better than those ofT-type tower. Thus it can be seen that the Z-type tower is more suitable to be applied in mountainous regions than T-type tower.
What problem does this paper attempt to address?