Analysis of Protection Effects of Using Side Needle on Ground Wires Against Shielding Failure in Transmission Line

沈志恒,赵斌财,周浩,龚坚刚,孙可,王东举
2012-01-01
Abstract:To study the lightning protection techniques of overhead transmission line,and to estimate the protection effect of side needle which was used against lightning shielding failure,using a 3D electro-geometrical model(EGM),we calculated the protection distance of side needle,and summarized its installation rule on ground wires.The calculation results of typical 110~500 kV lines show that side needle has a positive effect against shielding failure,but the protection distance of each needle is small.As a result,a large number of side needles are required to be installed on the ground wires in order to achieve good protection effect against shielding failure.And the relative positions of overhead line's conductor and ground wire have a great influence on the side needle's protection distance,showing that the side needle can only protect the single-circuit lines with small shielding angle and small tower size.For multi-circuit transmission lines,the side needle can not substantially help protect lightning shielding,mostly because of the large scale of the multi-circuit tower.In addition,the side needle has a negative impact on lines' mechanical properties after being installed on the ground wires.In conclusion,the side needle's protection effect is insufficient and can only be used on the particular types of transmission lines,which limits its applications in lightning protection against shielding failure.So the lightning protection measures need to be further improved and perfected.