Effects of Reducing Shielding Angle on Improving Lightning Performance of Transmission Lines

WANG Zhi-yong,YU Zhan-qing,LI Yu,LIANG Xi-dong
DOI: https://doi.org/10.13336/j.1003-6520.hve.2011.03.010
2011-01-01
Abstract:Lightning shielding failure is a key problem affecting operation safety of transmission lines,and reducing shielding angles is an important measure to restrain shielding failure rate.The shielding failure rate analyzing method for very high voltage transmission lines based on the leader progress model was introduced.By this method,effects of reducing shielding angles on different types of towers in various terrains were calculated and compared.An improved scheme of reducing shielding angles was proposed,and mechanical properties of the tower were analyzed.The cost of reducing shielding angle was evaluated,and its technical economy was compared to other lightning protection measures.Results show that shielding failure rate is closely related with tower types and terrains.In general,for the same tower,the shielding failure rate decreases with the decreasing of shielding angle,while for different towers,the shielding failure rates under the same shielding angle can be quite different.Effects of reducing shielding angle depend on the terrains.By comparing effects and costs of different lightning protection measures,it can be seen that increasing the distance of the ground lines is the optimal choice.
What problem does this paper attempt to address?