Transient Potential Distribution of Transmission Tower and Its Grounding Device under Lightning

ZHANG Bo,XUE Huizhong,JIN Zushan,YU Shaofeng,WU Jinpeng
DOI: https://doi.org/10.3969/j.issn.1003-6520.2013.02.020
2013-01-01
Abstract:In order to provide references for grounding resistance reduction and tower optimization which aim at reducing the lightning failure rate of transmission lines,the withstand voltages of a transmission tower and its grounding device under a lightning strike were analyzed using an numerical method of electromagnetic fields.The voltage distributions on the transmission tower and the grounding device were obtained by taking different conditions into consideration,such as parameters of the lightning waveform,height of the tower,soil resistance and size of the grounding device.The calculation results showed that,under a lightning stroke,a higher voltage peak on the tower resulted from a shorter front time of lighting wave,a higher height of the tower,a bigger grounding resistance,or a smaller size of the grounding device.Since reducing the grounding resistance can significantly decrease the continuous time of high voltage at the top of the tower,lowering the ground resistance of transmission towers in high soil resistivity areas is a good method for reducing the damage of lightning strokes.