Influence of Tower Grounding Resistance on Lightning Protection Performance of Transmission Lines with Multi-circuits on the Same Tower

Jinliang He
2011-01-01
Abstract:The grounding resistance of the transmission line towers is one of the most direct influential factors to the lightning withstand level and the back flash rate.To analyze the influences of the grounding resistance on the withstand level in different tower models and the influences of the grounding resistance on the withstand level of different circuits in multi-circuits tower,we analyzed the dependence of the tower grounding resistance to the lightning backflash withstand level and backflash rate using different tower models and different insulator models.With different tower models,the potential on the top of the tower and the withstand level would also be different,and this difference would decrease as the grounding resistance rises.When the tower grounding resistance increases to a certain level,the withstand level of the tower with different tower models would converge to one level.To the transmission lines with multi-circuits on the same tower,for the heights of different circuit conductors are different,the influence of the tower grounding resistance on different circuit would be distinct.The closer the conductor to the ground,the more remarkable the influence of the grounding resistance is.Finally,we calculated the influence of the tower grounding resistance on the withstand level of various phase conductors,and presented the suggested tower grounding resistance in design for transmission lines with multi-circuits on the same tower.