Influence of Mounting Location and Number of Coupling Ground Wires on Characteristic of Lightning Protection for 500/220kv Quadruple-circuit Transmission Line on Same Tower

Jinliang He
2012-01-01
Abstract:Mounting coupling ground wire is an effective lightning protection measure to reduce trip-out rate of back flashover,however,various mounting positions of coupling ground wire have different impacts on the lightning protection characteristics of transmission lines,especially the multi-circuit lines.We compared their protecting effect of setting single or two grounding wires in the middle of cross-arms at different heights,and analyzed the effects of mounting coupling ground wire on the center of different cross-arm aimed at 500/220 kV quadruple-circuit transmission lines.Moreover,in order to explore the mechanism of coupling grounding wires improving the protection characteristics in transmission lines,we compared and discussed the shunt coefficients of tower,ground wire and coupling ground wire and the coupling coefficient in the condition of various mounting positions.The results indicate that the effect of protecting conductor wire is better when the coupling ground wire is closer to the conductor.The shunt coefficient of single coupling ground wire can reach 2%~7%,and the shunt coefficient of double coupling ground wires can reach 5%~14%.Mounting coupling grounding wires can effectively increase the coupling coefficient.
What problem does this paper attempt to address?