Research on Lightning Transient Response of Grounding Grid of Communication Tower and Machine Room in High-speed Railway

YANG Jin,ZOU Jun
DOI: https://doi.org/10.3969/j.issn.1001-8360.2017.11.013
2017-01-01
Abstract:When the communication tower,which is always close to the mechanical equipment room,is struck by lightning,the potential of the grounding grid of the mechanical equipment room will be increased,in which the electronic equipment may be damaged.In this paper,firstly,the corresponding lightening transient calculation model was established,based on the construction drawings of the grounding grid of the communication towers and mechanical equipment room in the Baoji-Lanzhou high-speed railway system.On the basis of the model,an analysis was made on the changes of the potential of the grounding grid of the mechanical equipment room under the influence of different factors including the equal potential connection between two grounding grids,the distance between two grounding grids and the earth resistivity,when the communication tower was struck by lightening.The results showed that the transient potential of the grounding grid of the mechanical equipment room can be reduced by 70% when the distance between the two grounding grids increased from 5 m to 20 m.The existence of the equal potential connection would make the transient potential of the grounding grid of the mechanical equipment room increase 10 times.At last,some suggestions were proposed based on the research results.