Lightning Transient Performance Analysis of Substation Based on Complete Transmission Line Model of Power Network and Grounding Systems

R Zeng,P Kang,JL He,B Zhang,SM Chen,J Zou
DOI: https://doi.org/10.1109/tmag.2006.871462
IF: 1.848
2006-01-01
IEEE Transactions on Magnetics
Abstract:The grounding systems are simply handled as lumped resistances with constant values in traditional lightning transient analysis of substation. A complete transmission line model is proposed to consider the actual transient process of power network and the grounding grid of the substation and the grounding devices of transmission towers. A loss transmission line model with time-variable parameters is proposed to calculate the transient characteristics of grounding systems under lightning current in which the soil ionization phenomena around the ground conductors are considered. The analyzed results by the proposed model have large differences with those obtained by the traditional simplified method. The transient characteristics of grounding systems have strong influence on the lightning transient process of substation.
What problem does this paper attempt to address?